insulation monitoring device Vigilohm IM9-OL, 110 to 415VAC supply, for off-Line equipment

Product ID: 96073560 ! Pre Order
New New
Schneider Electric insulation monitoring device Vigilohm IM9-OL, 110 to 415VAC supply, for off-Line equipment IMD-IM9-OL | Elektrika.lv
New New
Schneider Electric insulation monitoring device Vigilohm IM9-OL, 110 to 415VAC supply, for off-Line equipment IMD-IM9-OL | Elektrika.lv

Price and quantity

* Price is valid while product is in stock. if a chosen item is out of stock at the moment, our specialists will inform you about delivery terms and prices.
(0)
  • e-store price

    709.46 / pcs

  • Quantity

  • Total price VAT included (21%)

    709.46

Availability

* The availability of a product in Elektrika warehouses is indicated below. If the product is in the supplier's warehouse, it may take up to 2-12 business days to arrive at Elektrika warehouse.
  • Riga (Marupe)

    0

  • Daugavpils

    0

  • Valmiera

    0

  • Ventspils

    0

Product details

* The displayed pictures may not match the product
  • Manufacturer

    Schneider Electric

  • Manufacturers ID

    IMD-IM9-OL

  • EAN

    3606480321665

  • Sustainable by Design
    Green Premium™
    Ilgtspējīgs iepakojums Sustainable Packaging
    Product primary packaging free from single-use plastic and uses recycled cardboard.
    Pārredzamība Transparency
    Assessment of the product environmental impacts along its life-cycle and availability of the data through a Product Environmental Profile.
    RoHS/REACh RoHS/REACh
    Compliant with RoHS/REACh regulations

Product parameters

  • Net Weight

    0.222 kg

  • Height

    85 mm

  • Length

    95 mm

  • Sustainability

    +

  • Width

    80 mm

Additional parameters

+
  • Depth

    67.5 mm

  • Error registration possible

    -

  • External power supply required

    -

  • Function

    For mixed system

  • Height

    90 mm

  • Indication of insulation value

    -

  • Line capacity

    60 µF

  • Number of contacts as change-over contact

    1

  • Number of contacts as normally closed contact

    0

  • Number of contacts as normally open contact

    0

  • Operating voltage at AC 50 Hz

    0 .. 690 V

  • Operating voltage at AC 60 Hz

    0 .. 690 V

  • Operating voltage at DC

    0 V

  • Rated control supply voltage Us at AC 50HZ

    110 .. 415 V

  • Rated control supply voltage Us at AC 60HZ

    110 .. 415 V

  • Rated control supply voltage Us at DC

    125 .. 250 V

  • Rated frequency

    45 .. 440 Hz

  • Rated operation frequency

    45 .. 440 Hz

  • Rated voltage

    0 .. 690 V

  • Response value impedance 1

    500 .. 10000 kOhm

  • Response value impedance 2

    250 .. 2000 kOhm

  • Supply voltage AC 50 Hz

    110 .. 415 V

  • Supply voltage AC 60 Hz

    110 .. 415 V

  • Supply voltage DC

    125 .. 250 V

  • Type of electric connection

    Screw connection

  • Voltage measurement range

    0 .. 690 V

  • Voltage type (operating voltage)

    AC

  • Voltage type for actuating

    AC

  • Voltage type of supply voltage

    AC/DC

  • Width

    71 mm

  • With detachable clamps

    -

Description

Vigilohm IM9-OL is an insulation monitoring device (IMD) permanently monitoring one offline equipment as per IEC 60364 requirements. According to standards, it is recommanded to equip your systems with Insulation Monitoring Devices (IMD). This device is dedicated to monitoring off line loads. It mesures the load insulation resistance by injecting a DC current between the network and ground. IM9-OL is versatile, adapting to networks resistance betwen 1k and 500 kOhm with an accuracy around 15% at 10 kOhm and 1 µF. To meet your applications, the device insulation alarm thresholds can be set between 250 kOhm and 10 MOhm. Once the alarm threshold is breached, it triggers an alarm that is relayed by 1 standard or fail-safe dry contact or by the local front face LED. A rotary switch on the front face defines whether or not a motor should be powered on if the insulation alarm threshold has been breached. It contributes to enhance people safety, limit installations damages and is mandatory for some building types in some countries. This IMD benefits installations where offline equipment cannot fail to power on in case of emergency (in TN, TT or IT earthing). The device can be supplied by a 110VAC to 415VAC or a 125VDC to 250VDC source, with 15% tolerance, plus or minus. It monitors offline equipment such as motors, fire pumps, ventilation systems or generators up to 690VAC. The relay can be manually tested with a self-test button to ensure that the monitoring of the offline equipment remains permanent. It has been designed according to EN/IEC 61557-8 product standard and has Marine certification. It can be DIN rail or flush-mounted to meet your installation. The HMI design makes it easy for the user to do device configurations, manual test, or to get informed about the device and network status. Vigilohm benefits from over 50 years' experience of insulation monitoring devices design by Schneider Electric. It is installed all over the world in tertiary buildings, industrial, marine, transportation, power generation or infrastructure sites.