Trip unit, TMD, 160A, 4p 4d. range of product: NSX100...250 - product compatibility: NSX160 - circuit breaker application: distribution - poles description: 4P - protected poles description: 4t - neutral position: left - network type: AC - network fr

Product ID: 3270274 ! Pre Order
Schneider Electric Trip unit, TMD, 160A, 4p 4d. range of product: NSX100...250 - product compatibility: NSX160 - circuit breaker application: distribution - poles description: 4P - protected poles description: 4t - neutral position: left - network type: AC - network fr LV430450 | Elektrika.lv

Price and quantity

* Price is valid while product is in stock. if a chosen item is out of stock at the moment, our specialists will inform you about delivery terms and prices.
(0)
  • e-store price

    194.23 / pcs.

  • Quantity

  • Total price VAT included (21%)

    194.23

Availability

* The availability of a product in Elektrika warehouses is indicated below. If the product is in the supplier's warehouse, it may take up to 2-12 business days to arrive at Elektrika warehouse.
  • Riga (Marupe)

    0

  • Daugavpils

    0

  • Valmiera

    0

  • Ventspils

    0

Product details

* The displayed pictures may not match the product
  • Manufacturer

    Schneider Electric

  • Manufacturers ID

    LV430450

  • EAN

    3606480018169

  • Sustainable by Design
    Green Premium™
    Ilgtspējīgs iepakojums Sustainable Packaging
    Product primary packaging free from single-use plastic and uses recycled cardboard.
    Pārredzamība Transparency
    Assessment of the product environmental impacts along its life-cycle and availability of the data through a Product Environmental Profile.
    RoHS/REACh RoHS/REACh
    Compliant with RoHS/REACh regulations

Product parameters

  • Net Weight

    0.503 kg

  • Height

    65 mm

  • Length

    98 mm

  • Sustainability

    +

  • Width

    150 mm

Additional parameters

+
  • End value adjustment range undelayed short-circuit release

    1250 A

  • Initial value of the undelayed short-circuit release - setting range

    1250 A

  • Number of poles

    4

  • Overload release current setting

    112 .. 160 A

  • Rated permanent current Iu

    160 A

  • Short-circuit release function

    Undelayed

  • Type of motor protection

    Thermal/magnetic release

  • Voltage type for actuating

    Self powered

  • With ground fault protection function

    -

Description

This TM160D is 4 poles 4d thermal-magnetic trip unit used on Compact NSX 160 circuit breakers. This 160A rating thermal-magnetic trip unit is an optimum choice for all distribution applications. It embeds an adjustable thermal overload protection and a fixed magnetic protection against short-circuits. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.