TeSys GV3-Circuit breaker-thermal-magnetic, 30…40A, EverLink BTR connectors. range: TeSys - device short name: GV3P - product or component type: circuit breaker - circuit breaker application: motor protection - network type: AC - utilisation category

Toote ID : 3671117 Laos
Schneider Electric TeSys GV3-Circuit breaker-thermal-magnetic, 30…40A, EverLink BTR connectors. range: TeSys - device short name: GV3P - product or component type: circuit breaker - circuit breaker application: motor protection - network type: AC - utilisation category GV3P40 | Elektrika.lv

Hind ja kogus

* Hinnad kehtivad, kuni kaupa jätkub. Kui antud toode on laost otsas, teavitavad meie spetsialistid teid tarneaegadest ja hindadest.
(0)
  • e-poe hind

    179.36 / pcs.

  • Kogus

  • Tasutav summa KM-ga (21%)

    179.36

Kättesaadavus

* Allpool on toodud kauba saadavus Elektrika filiaalides. Kui toode asub tarnija laos, võib tarneaeg Elektrika lattu võtta 2–12 tööpäeva.
  • Riga (Marupe)

    0

  • Daugavpils

    0

  • Valmiera

    2

  • Ventspils

    0

  • Tarnija ladu

    55

Teave toote kohta

* Piltidel vaid informatiivne tähendus
  • Tootja

    Schneider Electric

  • Tootja ID

    GV3P40

  • EAN

    3389119405393

  • Sustainable by Design
    Green Premium™
    Ilgtspējīgs iepakojums Sustainable Packaging
    Product primary packaging free from single-use plastic and uses recycled cardboard.
    Pārredzamība Transparency
    Assessment of the product environmental impacts along its life-cycle and availability of the data through a Product Environmental Profile.
    RoHS/REACh RoHS/REACh
    Compliant with RoHS/REACh regulations

Toote parameetrid

  • Netokaal

    0.982 kg

  • Kõrgus

    160 mm

  • Laius

    146 mm

  • Pikkus

    65 mm

  • Sustainability

    +

Täiendavad parameetrid

+
  • Adjustment range undelayed short-circuit release

    560 .. 560 A

  • Degree of protection (IP)

    IP20

  • Depth

    136 mm

  • Device construction

    Complete device in housing

  • Kõrgus

    132 mm

  • Laius

    55 mm

  • Number of poles

    3

  • Overload release current setting

    30 .. 40 A

  • Phase failure sensitive

    +

  • Power loss

    8 W

  • Rated operating voltage

    690 .. 690 V

  • Rated operation power at AC-3, 230 V

    11 kW

  • Rated operation power at AC-3, 400 V

    18.5 kW

  • Rated permanent current Iu

    40 A

  • Rated short-circuit breaking capacity lcu at 400 V, AC

    50 kA

  • Switch off technique

    Thermomagnetic

  • Type of control element

    Turn button

  • Type of electrical connection of main circuit

    Screw connection

  • With integrated auxiliary switch

    -

  • With integrated under voltage release

    -

  • With thermal protection

    +

Video

Tagasiside (0)

+ Lisada tagasiside
×
EE